ScreenMaster RVG200
Paperless recorder
7 Configuration
OI/RVG200-EN
87
Filter type
*
Select the filter to be applied to the electrical input prior to sampling.
Note.
Applicable to analog sources only.
Filters are applied to the recorded values shown on the Chart view
only, not to instantaneous values displayed on the channel
indicators.
Instantaneous
Average
Minimum
Maximum
Max & min
–
–
–
–
–
A single value based on process conditions at the
time of sampling.
The average value of the analog signal since the
previous sample.
The minimum value of the analog signal since the
previous sample.
The maximum value of the analog signal since the
previous sample.
Two values are recorded to capture the maximum and
minimum signal values since the previous sample.
This allows the memory use to be extended by
permitting a slower sample rate to be selected
without losing the transient behavior of the signal.
*
If this parameter is changed, internally-recorded data files are recreated and unarchived data is lost.