ScreenMaster RVG200
Paperless recorder
8 Specification
OI/RVG200-EN
137
8 Specification
Operation and configuration
Configuration
Via resistive touchscreen or PC Configuration
Multiple configuration files can be stored in internal
memory (up to 16 files) or external memory (SD card,
USB flash drive)
Display
Color, TFT, liquid crystal display (LCD) with LED
backlight and brightness adjustment
144 mm (5.7 in.) diagonal display area,
76800 pixel (
1
/
4
VGA) display *
* A small percentage of the display pixels may be either
constantly active or inactive. Maximum percentage of
inoperative pixels < 0.01 %
Language
English, German, French, Italian, Spanish, Chinese
Chart screen intervals
Selectable from 18 seconds to 7 days
Chart divisions
Programmable for up to 10 major and 10 minor
divisions
Chart annotation
Alarm, batch, electronic signatures and operator
messages may be annotated on the chart
Real-time clock
Security
Physical
Lockable media door
Front and rear tamper-evident seals
Configuration security
Logging security
Basic type security
4 individual users with unique user name and
passwords
Advanced type security
* User names are unique (names cannot be repeated)
Accuracy:
±5 ppm (±0.43 seconds per day)
Back-up battery: Battery low warning
Provides 3 years support for
unpowered condition
10 year shelf-life
Password
protection:
Access to configuration is enabled
only after the user has entered a
password
Internal switch
protection:
Access to configuration is enabled
only after a hardware switch has
been set. This switch is situated
behind a tamper-evident seal
Configuration:
Can be configured for password
protection or free access to
logging level
Number of
users:
Up to 40
User names: *
Up to 20 characters
Access
privileges:
Logging access – Yes / No
Configuration access – none / load
file only / limited / full
Passwords:
Up to 20 characters
A minimum required password
length of 4 to 20 characters can
be configured and a password
expiry time can be applied to
eliminate password ageing
Password failure
limit:
Configurable for 1 to 10
consecutive occasions or 'infinite'
A user is deactivated if a wrong
password is entered repeatedly
Deactivation of
inactive users:
Can be disabled or configured for
7, 14, 30, 60, 90, 180 or 360 days
of inactivity
Users are deactivated (by removal
of access privileges) after a period
of inactivity