8 Specification
OI/RVG200-EN
143
Advanced math (optional)
Type
24 equations provide ability to
perform general
arithmetic calculations including mass flow (of ideal
gases), relative humidity and emissions calculations
Size
40-character equation
Functions
+, –, /, log, Ln, Exp, Xn,
, Sin, Cos, Tan, mean, rolling
average, standard deviation, high / median / low select,
multiplexer, absolute, relative humidity
Tags
8- and 20-character tags for each block
Update rate
1 enabled Math block is updated every 125 ms
Logic equations (optional)
Number
24
Size
11 elements each
Functions
AND, OR, NAND, NOR, XOR, NOT
Tags
20-character tag for each equation
Update rate
300 ms
Totalizer (optional)
Number
48 (2 per recording channel) 10-digit totals
Type
Analog, digital or F
0
, batch, secure totals
Statistical calculations
Average, maximum, minimum (for analog signals)
6-Relay module
Number of relays
6 per module
Type and rating
Relay type single-pole changeover
Note.
The total load for all relays within the recorder
must not exceed 36 A.
Voltage:
250 V AC, 30 V DC
Current:
5 A AC, 5 A DC
Loading
(non-inductive):
1250 VA, 150