background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9502-A  Rev.6  P. 1 / 5

INSTRUCTION MANUAL

DC INPUT DIGITAL PANEL METER

(4 1/2 digit, LED display type)

MODEL

47LV

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Digital panel meter 
(body + mounting bracket × 2 + watertight packing) ........(1)
Engineering unit sticker label sheet ..................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.
For detailed explanations to operate and program the 
module, please refer to Model 47LV Operating Manual 
(EM-9502-B), downloadable at M-System’s web site: http://
www.m-system.co.jp.
2.00 marked parameters are usable with the product ver-
sion 2.00 or higher.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2, Meas-

urement category II (alarm output, transient voltage 
2500V) and Installation Category II (transient voltage 
2500V).  Reinforced insulation (input or DC output to 
alarm output to power: 300V) and basic insulation (input 
to DC output: 300V) are maintained. Prior to installation, 
check that the insulation class of this unit satisfies the 
system requirements.

• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• In order to enable the operator to turn off the power in-

put immediately, install a switch or a circuit breaker ac-
cording to the relevant requirements in IEC 60947-2 and 
properly indicate it.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 50/60 Hz, approx. 6.5VA
  24V DC rating: 24V ±10%, approx. 3W
  110V DC rating: 85 – 150V, approx. 3W

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

• Be sure to put the terminal cover on while the power is 

supplied. 

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C     

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

REQUIREMENTS TO ENSURE IP66

• Observe the designated panel cutout size (W92 

×

 H45 

mm).

• The watertight packing included in the product package 

must be placed behind the front cover.

• Both mounting brackets must be fastened tightly until 

they hit the panel.

• Confirm visually that the packing is not contorted or ex-

cessively run off the edge after installation.

 

WIRING

• Make sure for safety that only qualified personnel per-

form the wiring.

• Do not install cables  close to noise sources (high frequen-

cy line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

EX-FACTORY SETTING (/SET)

• Activating “initialization” of Lockout Setting Mode, Ex-

factory settings or user’s specified parameters will be 
deleted and overwritten with the factory default values.  
Notice that after this, Ex-factory settings will be irrecov-
erable.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Reviews: