ScreenMaster RVG200
Paperless recorder
7 Configuration
92
OI/RVG200-EN
Engineering range
*
Select the display characteristics of the input.
Low
High
Units
**
Specify the display range and units of the engineering value
corresponding to the electrical high and low values, within the limits
defined in Table 7.3.
THC / RTD type
°C
°F
Minimum Maximum Minimum Maximum
B
–18
1800
0
3270
E
–100
900
–140
1650
J
–100
900
–140
1650
K
–100
1300
–140
2350
L
–100
900
–140
1650
N
–200
1300
–325
2350
R & S
–18
1700
0
3090
T
–250
300
–400
570
Pt100
–200
600
–325
1100
Power 5/2
–99999 to +999999
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 7.3 Limits of engineering ranges
*
If this parameter is changed, internally-recorded data files are recreated and unarchived data is lost.
**
Due to the display resolution, if more than 2 channels are assigned to a group, engineering units featuring
a superscript 3 character (for example, m
3
) may not be displayed correctly in the Chart views.