Description
PSMH
PSML
Maximum interruption time in
the auxiliary DC without
resetting the RIO600 modules
100 ms at U
aux
nominal
50 ms at U
aux
nominal
Ripple in the DC auxiliary
voltage
Max. 15% of the DC value (at frequency of 100 Hz)
Reversal of DC power supply
polarity
1 minute for each polarity
Burden of auxiliary voltage
supply
•
Quiescent (Pq) condition
(none of the 20 I/O
channels are activated)
<4.0 W nominal
•
Operating condition (20
binary output channels in
DOM4 modules are
activated)
<12.0 W (maximum)
Module configuration
Condition
Max. consumption for PSMH
and PSML
PSM + LECM + DIM8H
All DIs activated
2 W
PSM + LECM + DIM8L
PSM + LECM + DOM4
All DOs activated
4 W
PSM + LECM + DOM4 (5)
All DOs activated
12 W
PSM (2) + LECM + DIM8H (5)
All DIs activated
11 W
PSM (2) + LECM + DIM8L (5)
PSM (2) + LECM + DOM4 (10)
All DOs activated
22 W
Table 191:
Binary inputs
Description
DIM8H
DIM8L
Rated voltage
110…250 V DC
24, 30, 48, 60 V DC
Operating voltage range
±20% of rated voltage
±20% of rated voltage
Current drain
3…3.7 mA
2 mA
Power consumption/input
channel
330…925 mW
30…130 mW
Threshold voltage
78 V DC
13 V DC
Reaction time
5 ms...4.0 s filtering time
5 ms...4.0 s filtering time
Table 192:
Signal outputs (digital output module DOM4)
Description
Value
Operating time
<5 ms
Nominal coil power
<500 mW
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Table continues on next page
Section 10
1MRS757488 H
Technical data
286
RIO600
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...