Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
1256
i32
1
.DmdVArh.actVal
Reactive Energy Demand
1257
1258
i32
1
.SupVArh.actVal
Reactive Energy Supply
1259
7.2.42
LD0.MFAPSDE multifrequency admittance protection
(earth-fault indication)
Table 167:
LD0.MFAPSDE multifrequency admittance protection
Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.MFAPSDE1
SIM8F-1
0 = unknown
1 = forward
2 = reverse
3 = both
1260
u16
1
.Str.dirGeneral
General Start
LD0.MFAPSDE2
SIM8F-2
1308
u16
1
.Str.dirGeneral
General Start
LD0.MFAPSDE3
SIM8F-3
1356
u16
1
.Str.dirGeneral
General Start
LD0.MFAPSDE4
SIM8F-4
1404
u16
1
.Str.dirGeneral
General Start
LD0.MFAPSDE5
SIM8F-5
1452
u16
1
.Str.dirGeneral
General Start
7.2.43
SCM Application types
Table 168:
IEC 61850 name for SCM application types
SCM application type
IEC 61850 name
Low voltage
High voltage
Four Input/Four Output
LD0.SCMLGGIO
LD0.SCMHGGIO
Three Position Switch
LD0.SCMLPGGIO
LD0.SCMHPGGIO
Two Position Disconnector
LD0.SCMLDGGIO
LD0.SCMHDGGIO
Two Position Earth
LD0.SCMLEGGIO
LD0.SCMHEGGIO
Circuit Breaker
LD0.SCMLCGGIO
LD0.SCMHCGGIO
1MRS757488 H
Section 7
Modbus TCP communication
RIO600
241
Installation and Commissioning Manual