defined with setting
Tilt angle
to compensate the measurement errors of residual
current and voltage measurement.
+90 deg
-90 deg
Tilt
angle
0 deg
REVERSE
REVERSE
FORWARD
FORWARD
Re(Yo)
Im(Yo)
+45 deg
Y
os um_CPS
_
Y
os um_CPS
_
Y
os um_CPS
_
Y
os um_CPS
_
GUID-540336CC-0720-4F42-A59F-E99FC96508CE V1 EN
Figure 71:
Directional characteristic of the MFAPSDE function
In case of unearthed network operation, adequate tilt angle must be
allowed to ensure dependable operation of MFAPSDE.
In
, phasors 1…4 demonstrate the behavior of the directional phasor in
different network fault conditions.
•
Phasor 1 depicts the direction of accumulated sum admittance phasor in case of
an earth fault outside the protected feeder (assuming that the admittance of the
protected feeder is dominantly capacitive). The result is valid regardless of the
fault type (low ohmic, high(er) ohmic, permanent or intermittent). In case
Section 6
1MRS757488 H
Commissioning
122
RIO600
Installation and Commissioning Manual