PSMH
Ready
RIO600
LECM
Ready
IRF
Rx/Tx
10M/100M
SIM8F
Ready
IRF
LF Fwd / Rv
THD / TDD
Non Dir OC
OC Fwd / Rv
Non Dir EF
EF Fwd / Rv
DIM8H
Ready
IRF
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
SIM4F
Ready
IRF
Inrush
Fault Pass
Non Dir OC
Neg Seq OC
Non Dir EF
DOM4
Ready
IRF
DO1
DO2
DO3
DO4
Volt Presence
GUID-749F7169-F4AD-4F30-B0E9-D535AEDB410C V3 EN
Figure 14:
RIO600 configuration: 1 × SIM8F + 1 × SIM4F + 1 × DIM8H + 1 ×
DOM4
5.2
Connecting wires
5.2.1
Connecting power supply
RIO600 supports power supply modules PSMH and PSML.
With the PSMH module, the voltage range for the external power connection is
110...250 V DC (±20%) and 100...240 V AC (-15% to +10%).
With the PSML module, the voltage range for the external power connection is U
aux
nominal 24, 30, 48, 60 V DC (with variation of 50...120% of Un) and the startup
threshold is 19.2 V DC (24 V DC * 80%).
1.
Fasten the power connector through the upper and lower screw terminals.
2.
Connect the power supply cable to the power supply module.
1MRS757488 H
Section 5
Installing
RIO600
33
Installation and Commissioning Manual