Signals
Table 43:
PEMMXU Input signals
Name
Type
Default
Description
I_A
SIGNAL
-
Phase A current
I_B
SIGNAL
-
Phase B current
I_C
SIGNAL
-
Phase C current
U_A
SIGNAL
-
Phase to earth voltage
A
U_B
SIGNAL
-
Phase to earth voltage
B
U_C
SIGNAL
-
Phase to earth voltage
C
Table 44:
PEMMXU Output signals
Name
Type
Description
VA.phsA cVal
REAL
Apparent power Phase A
W.phsA cVal
REAL
Active power Phase A
VAr.phsA cVal
REAL
Reactive power Phase A
VA.phsB cVal
REAL
Apparent power Phase B
W.phsB cVal
REAL
Active power Phase B
VAr.phsB cVal
REAL
Reactive power Phase B
VA.phsC cVal
REAL
Apparent power Phase C
W.phsC cVal
REAL
Active power Phase C
VAr.phsC cVal
REAL
Reactive power Phase C
TotVA
REAL
Total Apparent power
TotW
REAL
Total Active power
TotVAr
REAL
Total Reactive power
TotPF
REAL
Total Power Factor
Hz
REAL
System frequency
Table 45:
PEMMXU Technical data
Characteristic
Value
Operation accuracy
At frequency f = f
n
All three voltages are in the range of 9.6...14.4 kV
or 19.2...28.8 kV.
All three currents are in the range of 80...630 A.
Active power and energy are in the range |PF| >
0.71.
Reactive power and energy are in the range |PF| <
0.71.
±1.0% for active power P (±0.5% at +25ºC )
±3.0% for reactive Q and apparent power S (±1%
at +25ºC )
±0.03 for power factor
Suppression of harmonics
RMS: No suppression
1MRS757488 H
Section 6
Commissioning
RIO600
79
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...