LED
Color
State
Description
Non Dir Oc
Green
OFF
Non-directional
overcurrent fault
detection condition is
not detected
Non Dir Oc
Green
ON
Non-directional
overcurrent fault
detection condition is
detected
Neg Seq Oc
Green
OFF
Negative-sequence
overcurrent fault
condition is not
detected
Neg Seq Oc
Green
ON
Negative-sequence
overcurrent fault
condition is detected
Non Dir EF
Green
OFF
Non-directional earth-
fault detection
condition is not
detected
Non Dir EF
Green
ON
Non-directional earth-
fault detection
condition is detected
The binary input LED is ON if the input signal is HIGH (DIM8H:
~100 V DC, DIM8L: ~24 V DC) and OFF if the signal is LOW (~0 V
DC). The operation is independent of normal/inverted parameter.
The binary output LED is ON if the output contact is closed and OFF
if the output contact is open. The operation is independent of normal/
inverted parameter.
Flashing protection indication LEDs signify that the fault has been
cleared and is waiting for reset according to the
Fault indication reset
method
setting.
Table 178:
LED indicators (SCM module)
LED
Color
State
Description
Ready
Green
ON
Module is ready
Ready
Green
Flashing
Module is powered on,
configuration is
pending
IRF
Red
OFF
Module is healthy
Table continues on next page
Section 9
1MRS757488 H
Troubleshooting
276
RIO600
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...