Description
Type test value
Reference
•
Shock withstanding test
Peak acceleration: 15 g
Duration of the pulse: 11 ms
Number of pulses in each
direction: 3
•
Bump test
Peak acceleration: 10 g
Duration of the pulse: 16 ms
Number of pulses in each
direction: 1000
Seismic test
Class 2
IEC 60255-21-3
•
Nominal frequency range
1...35 Hz
•
Zero period acceleration
Horizontal direction: 2.0 gn
Vertical direction: 1.0 gn
•
Number of time histories in
each axis
Single axis sine sweep
Table 210:
Environmental tests
Description
Type test value
Reference
Dry heat test
•
96 h at +70°C
IEC 60068-2-2 and IEEE
C37.90-2005
Dry cold test
•
96 h at -25°C
•
16 h at -40°C
IEC 60068-2-1 and IEEE
C37.90-2005
Damp heat cyclic test
•
6 cycles (12 h + 12 h) at
+25...+55°C, humidity
>93%
IEC 60068-2-30
Damp heat steady state test
•
Temperature 40°C
•
Humidity 93%
•
Duration 96 h
IEC 60068-2-78 and IEEE
C37.90-2005
Change of temperature test
•
5 cycles (3 h + 3 h) at
-25...+55°C
IEC60068-2-14
Storage test
•
96 h at -40°C
•
96 h at +85°C
IEC 60068-2-1, IEC 60068-2-2
and IEEE C37.90-2005
Table 211:
EMC compliance
Description
Reference
EMC directive
2004/108/IEC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
Table 212:
RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
1MRS757488 H
Section 11
Device and functionality tests
RIO600
297
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...