Settings
Table 75:
DEFPTOC Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Start Value
4…200
200…1000
A
A
1
5
4
Start value for earth-
fault detection
Voltage Start Value
500..1000
V
1
500
Voltage start value
Operate Delay Time
40…60000
ms
10
80
Operate delay time
Enable Voltage Limit No
Yes
-
-
Yes
Additional check for
voltage before
issuing trip
Directional Mode
Forward
Reverse
Non Directional
-
-
Forward
Directional mode
Operation Mode
Phase angle
IoSin
IoCos
-
-
Phase angle
Operation criteria
Characteristics
Angle
-179…180
Deg
1
0
Characteristics
angle
Max Forward Angle
0…180
Deg
1
80
Maximum phase
angle in forward
direction
Max Reverse Angle
0…180
Deg
1
80
Maximum phase
angle in reverse
direction
Min Forward Angle
0…180
Deg
1
80
Minimum phase
angle in forward
direction
Min Reverse Angle
0…180
Deg
1
80
Minimum phase
angle in reverse
direction
Min Operate Current -
A
-
1
Minimum operating
current to allow
directional criteria
Min Operate Voltage -
V
-
500
Minimum operating
voltage to allow
directional criteria
Abs Hyst Oper Qty
0.0…50.0
A
0.1
0.1
Absolute hysteresis
for operating
quantity
Abs Hyst Pol Qty
0…2500
V
0.1
200
Absolute hysteresis
for polarizing
quantity
Section 6
1MRS757488 H
Commissioning
116
RIO600
Installation and Commissioning Manual