Name
Type
Description
OpRev
Boolean
Operate signal indicating fault in
reverse direction when
Directional mode is set to “Non
Directional”.
Str general
Boolean
General start signal
Str phsA
Boolean
Start signal for phase A
Str phsB
Boolean
Start signal for phase B
Str phsC
Boolean
Start signal for phase C
Str dirGeneral
Integer
General detected fault direction
Str dirPhsA
Integer
Detected fault direction for
phase A
Str dirPhsB
Integer
Detected fault direction for
phase B
Str dirPhsC
Integer
Detected fault direction for
phase C
Settings
Table 67:
DPHPTOC Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
No. of Start Phases
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases
required for operate
activation
Start Value
50…2000
A
10
480
Start value for
overcurrent fault
detection
Operate Delay Time
40…60000
ms
10
40
Operate delay time
Directional Mode
Forward
Reverse
Non-directional
-
-
Forward
Directional mode
Characteristics
Angle
-179…180
Deg
1
0
Characteristics
angle
Max Forward Angle
0…90
Deg
1
80
Maximum phase
angle in forward
direction
Max Reverse Angle
0…90
Deg
1
80
Maximum phase
angle in reverse
direction
Min Forward Angle
0…90
Deg
1
80
Minimum phase
angle in forward
direction
Min Reverse Angle
0…90
Deg
1
80
Minimum phase
angle in reverse
direction
Min Operate Current -
A
-
50
Minimum operating
current to allow
directional criteria
Table continues on next page
1MRS757488 H
Section 6
Commissioning
RIO600
99
Installation and Commissioning Manual