The
OP GENERAL
output is available at LED 5 of the SIM8F module.
The phase segregated as well as general start and operate outputs
STR GENERAL
,
STR PHSA
,
STR PHSB
,
STR PHSC
,
OP GENERAL
,
OP PHSA
,
OP PHSB
and
OP
PHSC
are available over communication.
Signals
Table 60:
PHPTOC Output signals
Name
Type
Description
Op general
Boolean
General operate signal
Op phsA
Boolean
Operate signal for phase A
Op phsB
Boolean
Operate signal for phase B
Op phsC
Boolean
Operate signal for phase C
Str general
Boolean
General start signal
Str phsA
Boolean
Start signal for phase A
Str phsB
Boolean
Start signal for phase B
Str phsC
Boolean
Start signal for phase C
Settings
Table 61:
PHPTOC Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
No. of Start Phases
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases
required for operate
activation
Start Value
50…2000
A
10
480
Start value for
overcurrent fault
detection
Operate Delay Time
40…60000
ms
10
40
Operate delay time
Absolute Hysteresis
0.0…100.0
A
0.1
3.0
Absolute hysteresis
for current
Table 62:
PHPTOC Technical data
Charateristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f = f
n
±1.5% of the set value
Operate time accuracy (DMT)
±1.0% of the set value or ±20 ms
1MRS757488 H
Section 6
Commissioning
RIO600
91
Installation and Commissioning Manual