6.1.6
Operating parameter settings of SIM8F module
Table 28:
Operating parameter settings of SIM8F module
Parameter name
Range
Unit
Step
Default
Description
Frequency
50
60
Hz
-
50 Hz
Rated system
frequency
Nominal current
80…630
A
1
400
Nominal phase
current
Nominal voltage
500…48000
V
1
15000
Nominal phase-
to-phase voltage
Rated sensor current
80
250
A
-
80
Rated primary
current of sensor
Io signal sel
Calculated Io
Measured Io
-
-
Calculated Io
Selection used
for Io signal
Phase Rotation
ABC
ACB
-
-
ABC
Phase rotation
order
Sensor Correction Factors
Phase A
Current
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for current
sensor, phase A
Current Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for current
sensor, phase A
Voltage
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for voltage
sensor, phase A
Voltage Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for voltage
sensor, phase A
Phase B
Current
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for current
sensor, phase B
Current Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for current
sensor, phase B
Voltage
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for voltage
sensor, phase B
Voltage Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for voltage
sensor, phase B
Table continues on next page
1MRS757488 H
Section 6
Commissioning
RIO600
69
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...