Section 10
Technical data
Table 187:
Interfaces
Description
Value
LECM Ethernet interface
RJ-45 (STP CAT5e) galvanic connector
Multimode LC fiber-optic connector
Power Supply Module (PSMH/PSML/DIM8H/
DIM8L/DOM4/SCM8H/SCM8L) front mating
connector
Suggested part: Weidmuller P/N 1844260000
Sensor input module SIM8F/SIM4F
Table 188:
Module weights
Description
Value
PSMH/PSML
235 g
LECM
123 g
DIM8H/DIM8L
206 g
DOM4
163 g
RTD4
206 g
AOM4
206 g
SIM8F/SIM4F
180 g
SCM8H/SCM8L
215 g
Table 189:
Dimensions of the end clamp (EW 35, Weidmuller)
Description
Value
Width
8.5 mm (to be fixed at the ends of assembled
modules)
Table 190:
Power supply
Description
PSMH
PSML
U
aux
nominal
100, 110, 120, 220, 240 V AC,
50 and 60 Hz
24, 30, 48, 60 V DC
110, 125, 220, 250 V DC
U
aux
variation
85…110% of U
aux
nominal
(85...264 V AC)
50...120% of U
aux
nominal
(12...72 V DC)
80…120% of U
aux
nominal
(88…300 V DC)
Start-up threshold
19.2 V DC (24 V DC × 80%)
Table continues on next page
1MRS757488 H
Section 10
Technical data
RIO600
285
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...