Parameter name
Range
Unit
Step
Default
Description
Phase C
Current
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for current
sensor, phase C
Current Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for current
sensor, phase C
Voltage
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for voltage
sensor, phase C
Voltage Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for voltage
sensor, phase C
Residual
Current
Amplitude
0.7000…1.3000
-
0.0001
1.0000
Amplitude
correction factor
for current
sensor, residual
Current Phase
-3.0000…
+3.0000
deg
0.00025
0.000
Phase correction
factor for current
sensor, residual
LED Reset Time Delay
1…1440
min
1
60
LEDs Reset
delay time
(incase no
external signal
received for
resetting). This is
applicable to
THD/TDD, OC
and EF fault
indication LEDs.
Default Load Flow Direction
Forward,
Reverse
-
-
Forward
Load flow
direction
selection. The
load flow
direction LED
color for Forward
selection is,
Forward =
Green, Reverse
= Red and vice
versa.
THD & TDD LED colors
THD = Red, TDD
= Green
THD = Green,
TDD = Red
-
-
THD = Green
TDD = Red
THD & TDD LED
indication
Protection LED Colors
Forward = Red,
Reverse = Green
Forward =
Green, Reverse
= Red
-
-
Forward = Green
Reverse = Red
Over Current
Direction LED
indication
Common setting
for DOC and
DEF
Table continues on next page
Section 6
1MRS757488 H
Commissioning
70
RIO600
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...