Description
Type test value
Reference
Pulsed magnetic field
1000 A/m; 6.4/16 μs Tr/Td; 5
pulses positive/negative; 10 s
(time interval)
IEC 61000-4-9, Level 5
Conducted disturbance induced
by radio frequency fields,
Amplitude modulated
0.15...80 MHz - 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
27 and 68 MHz (spot
frequencies); 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
IEC 60255-26 and IEC
61000-4-6, Level 3
Fast low-energy transient (EFT)
(including functional earth port)
5/50 ns Tr/Td; 5 kHz repetition
frequency
4 kV (peak) for power supply
input/output ports and 2 kV
(peak) for communication port
IEC 60255-26 and IEC
61000-4-4
Damped oscillatory waves
(HFD) 100 kHz and 1 MHz burst
100 kHz and 1 MHz frequency;
75 ns Tr; 40 Hz and 400 Hz
repetition frequency; 200 Ω
source impedance
IEC 60255-26 and IEC
61000-4-18
•
Power supply and input/
output ports
Differential mode: 1 kV (peak)
Common mode: 2.5 kV (peak)
•
Communication port
Differential mode: not applicable
Common mode: 1 kV (peak)
Slow high-energy transient
(surge1.2/50 μs voltage pulse)
1.2/50 μs Tr/Th (open circuit)
8/20 μs Tr/Th (short circuit)
IEC 60255-26 and IEC
61000-4-5
•
Auxiliary power supply and
input/output ports
1)
±4 kVp (L-Gnd) ±2 kVp (L-L)
•
Communication port
±2 kVp (L-Gnd) while no L-L test
is applicable
Voltage dips, short interruptions
and voltage variation immunity
tests (AC 50 Hz and 60 Hz)
30% reduction for 25/30 cycles
60% reduction for 10/12 cycles
100% reduction for 0.5, 1.0, 2.5
and 5.0 cycles
100% reduction for 250/300
cycles
IEC 60255-26 and IEC
61000-4-11
Voltage dips, supply interruption
and voltage variations on DC
input power port (immunity
tests)
30% reduction for 500 ms
60% reduction for 200 ms
100% reduction for 10, 20, 30
and 50 ms
100% reduction for 5 s
IEC 60255-26 and IEC
61000-4-29
Ripple voltage
15% U
n
frequencies of ripple
100/120 Hz (for 50/60 Hz)
IEC 60255-26, IEC 61000-4-17
and IEEE C37.90-2005
Gradual shut-down/start-up test
(for DC power supply)
IEC 60255-26
•
Ramp towards shut-down
60 s
•
Wait at power of condition
5 min
•
Ramp towards start-up
60 s
Power frequency voltage 50 Hz
and 60 Hz
Input/output port
IEC 60255-26 and IEC
61000-4-16
Table continues on next page
1MRS757488 H
Section 11
Device and functionality tests
RIO600
295
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...