7.2.13
LD0.VMHAI voltage total demand distortion
Table 138:
LD0.VMHAI voltage total demand distortion
Bit A
Reg A
IEC 61850 name
SA name
Description
Values
LD0.VMHAI1
SIM8F-1
533
385.05
.HiAThd.stVal
Voltage THD
1 = Operate
LD0.VMHAI2
SIM8F-2
565
387.05
.HiAThd.stVal
Voltage THD
1 = Operate
LD0.VMHAI3
SIM8F-3
661
801.05
.HiAThd.stVal
Voltage THD
1 = Operate
LD0.VMHAI4
SIM8F-4
693
803.05
.HiAThd.stVal
Voltage THD
1 = Operate
LD0.VMHAI5
SIM8F-5
725
805.05
.HiAThd.stVal
Voltage THD
1 = Operate
7.2.14
LD0.EFPTOC non-directional earth-fault detection
Table 139:
LD0.EFPTOC non-directional earth-fault detection
Bit A
Reg A
IEC 61850 name
SA name
Description
Values
LD0.EFPTOC1
SIM8F-1/SIM4F-1
534
385.06
.Str.general
START
General Start
1 = Start
535
385.07
.Op.general
Operate
General Operate
1 = Operate
LD0.EFPTOC2
SIM8F-2/SIM4F-2
566
387.06
.Str.general
START
General Start
1 = Start
567
387.07
.Op.general
Operate
General Operate
1 = Operate
LD0.EFPTOC3
SIM8F-3/SIM4F-3
662
801.06
.Str.general
START
General Start
1 = Start
663
801.07
.Op.general
Operate
General Operate
1 = Operate
LD0.EFPTOC4
SIM8F-4/SIM4F-4
694
803.06
.Str.general
START
General Start
1 = Start
695
803.07
.Op.general
Operate
General Operate
1 = Operate
LD0.EFPTOC5
SIM8F-5/SIM4F-5
726
805.06
.Str.general
START
General Start
1 = Start
727
805.07
.Op.general
Operate
General Operate
1 = Operate
1MRS757488 H
Section 7
Modbus TCP communication
RIO600
211
Installation and Commissioning Manual