Table 49:
EMMTR Output signals
Name
Type
Description
DmdWh
REAL
Accumulated forward active
energy value in kWh
SupWh
REAL
Accumulated reverse active
energy value in kWh
DmdVArh
REAL
Accumulated forward reactive
energy value in kVArh
SupVArh
REAL
Accumulated reverse reactive
energy value in kVArh
Table 50:
EMMTR Technical data
Characteristic
Value
Operation accuracy
At frequency f = fn
All three voltages are in the range of 9.6...14.4 kV
or 19.2...28.8 kV.
All three currents are in the range of 80...630 A.
Active power and energy are in the range |PF| >
0.71.
Reactive power and energy are in the range |PF| <
0.71.
±3.0% for energy
Suppression of harmonics
RMS: No suppression
Current, voltage and power average and peak measurement CMSTA,
VMSTA, PEMSTA
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current, voltage and power average and
peak measurement
CMSTA,
VMSTA,
PEMSTA
-
-
Section 6
1MRS757488 H
Commissioning
82
RIO600
Installation and Commissioning Manual