Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
0.06
Bit
Module 5 Health
0 = Ok,
1 = Warning
or error
0.07
Bit
Module 6 Health
0 = Ok,
1 = Warning
or error
0.08
Bit
Module 7 Health
0 = Ok,
1 = Warning
or error
0.09
Bit
Module 8 Health
0 = Ok,
1 = Warning
or error
0.1
Bit
Module 9 Health
0 = Ok,
1 = Warning
or error
0.11
Bit
Module 10 Health
0 = Ok,
1 = Warning
or error
0.12
Bit
UPS Power Failure Status
0 = Ok,
1 = Warning
or error
0.13
Bit
Local/Remote Mode Status
0 = Remote,
1 = Local
0.14
Bit
<reserved>
0
0.15
Bit
<reserved>
0
7.2.2
SSR2 System status register (2) device alive register
This register provides information about the Modbus device alive counter.
Table 127:
SSR2 System status register (2) device alive register
Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
1
u16
1
Device Alive Counter
0...65535
7.2.3
Time synchronization
RIO600 time can be synchronized with the Modbus client by writing to the register
addresses in
. The time can also be read from the same register addresses.
Table 128:
Time synchronization
Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
8
u16
1
Year
2000...2999
9
u16
1
Month
1...12
10
u16
1
Day
1...31
11
u16
1
Hour
0...23
12
u16
1
Minute
0...59
13
u16
1
Second
0...59
1MRS757488 H
Section 7
Modbus TCP communication
RIO600
185
Installation and Commissioning Manual