COM for DI1 and DI2
close control
52b
52a
OPEN COIL
CLOSE COIL
R
CB OPEN
CB CLOSE
CB READY
COM for DI3 and DI4
-V
AUX
+V
AUX
-V
AUX
-V
AUX
relay compartment
circuit breaker compartment
CB
SCM8H / SCM8L
X1
0V-
DI1
DI2
DI3
DI4
0V-
DI1
DI2
DI3
DI4
HS1
HS2
HS3
HS4
HS1
HS2
HS3
HS4
X2
GUID-B1267BF8-65D3-404B-A22B-35BAC79B7F18 V3 EN
Figure 30:
Connection diagram for circuit breaker application with trip circuit
supervision (direct tripping - double pole)
Table 18:
SCM connection for circuit breaker application
X1
Connector
inputs
Description
X2
Connector
outputs
Description
OV-
1
Common
return for for
DI1 and DI2
-
1
AUX. DC
voltage L-
DI1
2
Position
indication for
CB Open
HS1
2
CB OPEN Trip
coil
DI2
3
Position
indication for
CB Close
HS2
3
CB CLOSE
coil
Table continues on next page