GUID-0D76E7F2-D359-42D6-B774-D1E8D37EF4D6 V1 EN
Figure 82:
Configuring the UPS power failure input channel
6.1.6.11
Calibration
The SIM8F module is factory calibrated.
6.1.7
Operating parameter settings of SIM4F module
Table 97:
Operating parameter settings of SIM4F module
Parameter name
Range
Unit
Step
Default
Description
Frequency
50
60
Hz
-
50 Hz
Rated system
frequency
Nominal current
80…630
A
1
400
Nominal phase
current
Rated sensor current
80
250
A
-
80
Rated primary
current of sensor
Io signal sel
Calculated Io
Measured Io
-
-
Calculated Io
Selection used
for Io signal
Phase Rotation
ABC
ACB
-
-
ABC
Phase rotation
order
Sensor Correction Factors
Table continues on next page
1MRS757488 H
Section 6
Commissioning
RIO600
147
Installation and Commissioning Manual