Function block
CMSTA, VMSTA, PEMSTA
I_A
I_B
I_C
AvAmpsA
U_A
U_B
U_C
MaxAmpsA
AvAmpsB
MaxAmpsB
AvAmpsC
MaxAmpsC
AvW
MaxW
AvVAr
MaxVAr
AvVA
MaxVA
I0
BLOCK
GUID-7128BA48-98A5-4CF2-9774-E5ED6614A387 V1 EN
Figure 47:
Function block
Functionality
The current, voltage and power average and peak measurement functions CMSTA,
VMSTA and PEMSTA are used to calculate the average and peak value of current,
voltage and power. The functions can be enabled and disabled with the
Operation
setting.
The corresponding parameter values are "On" and "Off". The average interval can be
set to "3","10", "15", "60", "120", or "1440" minutes and the peak interval to "1 day",
"1 week", "1 month", or "1 year".
Signals
Table 51:
CMSTA, VMSTA & PEMSTA Input signals
Name
Type
Default
Description
I_A
REAL
-
Phase A current
I_B
REAL
-
Phase B current
I_C
REAL
-
Phase C current
U_A
REAL
-
Phase to earth voltage
A
U_B
REAL
-
Phase to earth voltage
B
U_C
REAL
-
Phase to earth voltage
C
Io
REAL
-
Residual current
BLOCK
-
-
Block through settings
only
1MRS757488 H
Section 6
Commissioning
RIO600
83
Installation and Commissioning Manual