
Table 40:
RESVMMXU Output signals
Name
Type
Description
PhV.res cVal.mag.f
REAL
Calculated magnitude of
residual voltage
PhV.res cVal.ang.f
REAL
Calculated residual voltage
angle
Table 41:
RESVMMXU Technical data
Characteristic
Value
Operation accuracy
At frequency f = f
n
±5.0% (when all three voltages are in the range of
9.6...14.4 kV or 19.2...28.8 kV)
Suppression of harmonics
RMS: No suppression
Three-phase power and energy measurement PEMMXU
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase power and energy
measurement
PEMMXU
P
P
Function block
PEMMXU
I_A
I_B
I_C
VA.phsA cVal
U_A
U_B
U_C
W.phsA cVal
VAr.phsA cVal
VA.phsB cVal
W.phsB cVal
VAr.phsB cVal
VA.phsC cVal
W.phsC cVal
VAr.phsC cVal
TotVA
TotW
TotVAr
TotPF
Hz
GUID-78BA8F95-76F5-4348-9A01-BCDB6750D41F V1 EN
Figure 42:
Function block
Power and energy calculation
The three-phase power is calculated from the phase-to-earth voltages and currents.
The power measurement function is capable of calculating a complex power based on
the fundamental frequency component (DFT).
Once the complex apparent power is calculated, P, Q, S and pf are calculated using
equations.
1MRS757488 H
Section 6
Commissioning
RIO600
77
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...