Table 199:
Communication interface (communication module LECM)
Connector Cable
Data transfer Maximum
distance
Wave length
Permitted
path
attenuation
1)
RJ-45
Shielded twisted pair
cable, at minimum CAT5e
10/100
Mbits/s
30 m
-
-
LC
Multimode 62.5/125 μm or
50/125 μm glass-fiber core
100 Mbits/s
2 km
1310 nm
<8 dB
1) Maximum allowed attenuation caused by connectors and cable together
Table 200:
Degree of protection by enclosure
Description
Value
Degree of protection
IP20
1)
1) If a higher IP class is required, the cabinet where the device is installed should provide proper
protection.
Table 201:
Environmental conditions
Description
Value
Operating temperature range
-25...+70°C
Relative humidity
<93%
Atmospheric pressure
86...106 kPa
Altitude
up to 2000 m
Transport and storage temperature range
-40...+85°C