Description
Value
Make and carry for 3.0 s
10 A
Make and carry for 0.5 s
15 A
Breaking capacity when the control circuit time
constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Table 193:
mA/RTD input (RTD4 module)
Description
Value
RTD inputs
Supported RTD
sensors
100 Ω platinum
TCR 0.00385 (DIN
43760)
250 Ω platinum
TCR 0.00385
100 Ω nickel
TCR 0.00618 (DIN
43760)
120 Ω nickel
TCR 0.00618
250 Ω nickel
TCR 0.00618
Maximum lead
resistance (three-wire
measurement)
100 Ω platinum
200 Ω per lead
250 Ω platinum
200 Ω per lead
100 Ω nickel
200 Ω per lead
120 Ω nickel
200 Ω per lead
250 Ω nickel
200 Ω per lead
Isolation
4 kV
Inputs to all other
channel outputs and
protective earth
RTD/resistance
sensing maximum
0.275 mA rms current
Operation accuracy
±1°C
Response time
< Filter time + 350 ms
mA inputs
Supported current
range
0…20 mA
Current input
impedance
44 Ω ± 0.1%
Operation accuracy
±0.5% or ±0.1 mA
Isolation
4 kV
Inputs to all outputs and
protective earth
Table 194:
Analog output module (AOM4)
Description
Value
mA output
Supported current
range
0.0…20.0 mA
Operation accuracy
±0.1% or ±0.2 mA
Isolation
4 kV between each output and protective earth
1MRS757488 H
Section 10
Technical data
RIO600
287
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...