Signals
Table 99:
FPIPTOC Input signals
Name
Type
Default
Description
IA
SIGNAL
0
Phase A current, IA
IB
SIGNAL
0
Phase B current, IB
IC
SIGNAL
0
Phase C current, IC
Table 100:
FPIPTOC Output signals
Name
Type
Description
FPIPTOC_Oper
BOOLEAN
Fault passage indication
function is started.
FPIPTOC_Start
BOOLEAN
Fault passage indication
function is operated.
Settings
Table 101:
FPIPTOC Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Residual Start Cur
1…100
A
1
4
Residual current
start threshold
EF Start Cur
1…100
A
1
4
Earth-fault current
start threshold
Inst Start Cur
10…100
A
1
50
Earth-fault current
threshold for
instantaneous start
condition
Angle Sector
10…90
Deg
1
15
Phase angle sector
boundary threshold
for fault passage
Operate Delay Time
100…60000
ms
10
500
Operate delay time
Ratio EF to Res Cur
0.1-1.0
0.1
0.1
Ratio earth-fault
current to residual
current
Start Delay Time
0...1000
ms
10
20
Start delay
Angle Offset Sector
10…90
Deg
1
45
Phase angle offset
threshold for fault
passage indication
Reset Delay Time
20…6000
ms
1
20
Reset Delay Time
Revert Time
300…1500
ms
10
300
Revert time for delta-
calculation
Section 6
1MRS757488 H
Commissioning
158
RIO600
Installation and Commissioning Manual