Load current
As baseline there is no integrated fuse or circuit breaker. The option 3008-3 Mains
connector/Fuse includes integrated circuit breaker.
Add an external circuit breaker (class K) according to full load current, as marked
on the controller nameplate. The following table shows the recommended rating
for an external fuse or circuit breaker.
Current (A)
Voltage (V)
Robot
3x32 A
380 VAC-480 VAC, 3-phase
IRB 4600
3x32 A
380 VAC-480 VAC, 3-phase
IRB 5710
3x32 A
380 VAC-480 VAC, 3-phase
IRB 5720
3x32 A
380 VAC-480 VAC, 3-phase
IRB 6700
Note
For details about installations according to UL requirements, see
Connecting
incoming mains and protective earth to the controller
chapter in
Product
manual - OmniCore V250XT
.
Residual current
An external earth fault protection (residual current device, RCD) is required based
on the following data:
Residual Current in controller (mA)
Robot
< 30 mA
IRB 4600
< 30 mA
IRB 5710
< 30 mA
IRB 5720
< 30 mA
IRB 6700
Note
The integrator is responsible to address local electrical requirements.
40
Product manual - OmniCore V250XT
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
2 Controller description
2.2 Technical data for OmniCore V250XT controller
Continued
Summary of Contents for OmniCore V250XT
Page 1: ...ROBOTICS Product manual OmniCore V250XT ...
Page 34: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 174: ...This page is intentionally left blank ...
Page 410: ...This page is intentionally left blank ...
Page 418: ...This page is intentionally left blank ...
Page 454: ......
Page 455: ......