Troubleshooting flowchart
Problem starting or
connecting the FlexPendant
Check LEDs:
HMI & PC
Not lit
Troubleshoot robot signal
exchange proxy K2
Check:
K2.X8 - A2.X6
K2.X2 - A2.X1
K2.X12 - A2.K3.X6,7
K2.X3 - A2.K3.X1
Green
Connection ok
Connection not ok
Repair connection
Check FlexPendant
cable
Cable
damaged
Cable ok
Check connection
K2.X13 to X4
Check connector X4
Connection
not ok
Connection
not ok
Connections ok
Start FlexPendant
Problem solved
Ok
Not starting
Replace FlexPendant
Replace FlexPendant
cable
Reset the
FlexPendant
xx2100001144
Continues on next page
366
Product manual - OmniCore V250XT
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
7 Troubleshooting
7.2.5 Problem starting or connecting the FlexPendant
Continued