7.2.2 Start-up failure
Description
The following are possible symptoms of a start-up failure:
1 The LEDs are not lit on some units.
2 Unable to load the system software.
Required test equipment
Equipment needed for troubleshooting:
Note
Equipment
Multimeter
Insulating gloves
3HAC074000-008
Circuit diagram - OmniCore V250XT
Preparations
Action
Make sure that the controller is switched on.
1
Wait 30 s - 1 min to enable start-up sequence.
Check the FlexPendant for errors and warnings.
2
DANGER
Troubleshooting on the controller while powered on must be performed by personnel
trained by ABB or by ABB field engineers.
Continues on next page
356
Product manual - OmniCore V250XT
3HAC073447-001 Revision: B