![ABB OmniCore V250XT Product Manual Download Page 387](http://html.mh-extra.com/html/abb/omnicore-v250xt/omnicore-v250xt_product-manual_5109387.webp)
Note
Action
Turn off power to the unit for 10 seconds and
restart. Check if the 24V_TRUNK voltage has
recovered.
Disconnect A1.X6 24V_TRUNK
from the power unit and restart.
6
Verify that the input to A1.X6 is 25.2 VDC -5%,
+5%.
•
If the measured voltage is normal with
A1.X6 disconnected, the load attached
to the power unit is causing the unit to
trip, see
Troubleshooting the robot signal
•
If the measured voltage is abnormal with
A1.X6 disconnected, the unit may be
faulty, see
.
•
If the error message is insufficient, pro-
ceed with step
.
•
If an error was resolved, restart from step
Check error message on FlexPend-
ant and take appropriate action.
7
Turn off power for 10 seconds.
Disconnect loads and test start.
8
Disconnect the following loads:
•
DC_OUT (X4 and X8, Drive unit)
•
AC_OUT (X7 and X15, External AC Sup-
ply to customer power supply)
•
24V_TRUNK (X6, Robot signal exchange
proxy)
•
24V_BRAKE (X11 and X14, Drive unit)
Turn on power again.
•
If the MODULE STATUS LED is green
with the loads disconnected, Proceed
with step
.
•
If the fault remains, the unit may be
faulty, see
.
If the connection and cables seem OK, proceed
with step
Make sure that the cables are con-
nected properly at both ends:
•
DC_OUT (X4 and X8)
•
AC_OUT (X7 and X15)
•
24V_TRUNK (X6)
•
24V_BRAKE (X11 and X14)
9
If there is a problem with the connection, pro-
ceed with step
.
If the connection and cables seem OK, proceed
with step
Replace cables:
•
DC_OUT (X4 and X8)
•
AC_OUT (X7 and X15)
•
24V_TRUNK (X6)
•
24V_BRAKE (X11 and X14)
10
If there is a problem with the connection, the
connected loads are out of specification. Con-
tact your local ABB.
Verify that 24V SYS DRV IN (X9) is stable at 24
VDC (18VDC – 26.4VDC).
•
If the measured voltage is normal and
MODULE STATUS LED is flashing green,
the unit has internal communication er-
ror, see
.
•
If the measured voltage is abnormal, see
Troubleshooting the robot signal ex-
change proxy on page 405
Verify 24V_SYS.
11
Continues on next page
Product manual - OmniCore V250XT
387
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
7 Troubleshooting
7.3.4 Troubleshooting the power unit
Continued
Summary of Contents for OmniCore V250XT
Page 1: ...ROBOTICS Product manual OmniCore V250XT ...
Page 34: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 174: ...This page is intentionally left blank ...
Page 410: ...This page is intentionally left blank ...
Page 418: ...This page is intentionally left blank ...
Page 454: ......
Page 455: ......