142 Communication protocol
Parameter data transfer examples (DP-V0)
Note:
Only the ‘data unit’ part of the telegram is presented in the
examples. See section
PROFIBUS SD2 telegram for Default SAP
.
Example 1: Reading a drive parameter (or data set)
To determine the parameter number and subindex for drive
parameter reading, convert the drive parameter group number and
the parameter index number to hexadecimal. The index number is
the
Subindex
(IND), and the group number is the
Parameter
Number
(PNU). For example, to read parameter
84.11
from the
drive:
84.11
= 54h.0Bh => Parameter Number = 54h, Subindex = 0Bh.
Req
D
P
h
ead
er 6
0
5
4
0
B
0
0
0
0
0
0
0
0
0
0
0
4
7
F
3
4
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DP tr
aile
r
Resp
4
0
5
4
0
B
0
0
0
0
0
0
0
0
6
4
0
3
3
7
3
4
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
CW
REF
PZD3 PZD4 PZD5 PZD6
Request (Read parameter value [array])
Parameter Number
Subindex
1)
SW
ACT
PZD3 PZD4 PZD5 PZD6
Parameter Value (100 decimal)
Subindex
1)
Parameter Number
Response (Read parameter value [array])
1)
2nd byte reserve
d
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...