80 Start-up
51.01 FBA A type
1
= FPBA
1)
Displays the type of the
fieldbus adapter module.
51.02 FBA A Par2
3
2)
Defines the PROFIBUS node
address of the fieldbus
adapter module.
51.03 Baud rate
12000
1)
Displays the current baud
rate on the PROFIBUS
network in kbit/s.
51.04 MSG type
1
= PPO1
1)
Displays the telegram type
selected by the PLC
configuration tool.
51.05 Profile
0
= PROFIdrive
Selects the Control word
according to the PROFIdrive
profile (speed control mode).
51.07 Emul mode
0
= Disabled
Disables the emulation
mode.
52.01 FBA A data in1
4
=
SW 16bit
1)
Status word
52.02 FBA A data in2
5
= Act1 16bit
Actual value 1
52.03 FBA A data in3
1.7 [32]
2)
Motor current
52.05 FBA A data in5
1.11 [32]
2)
DC voltage
53.01 FBA A data out1
1
= CW 16bit
1)
Control word
53.02 FBA A data out2
2
= Ref1 16bit
Reference 1 (speed)
53.03 FBA A data out3
22.26 [32]
2)
Constant speed 1
53.05 FBA A data out5
22.27 [32]
2)
Constant speed 2
51.27 FBA A par
refresh
1
= Refresh
Validates the FPBA-01
configuration parameter
settings.
19.12 Ext1 control
mode
2
= Speed
Selects speed control as the
control mode 1 for external
control location 1.
Drive parameter
Setting for
ACS880 drives
Description
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...