Start-up 57
5402 FBA DATA IN 2
5
(= Act1 16bit)
1)
Actual value 1 (speed)
5403 FBA DATA IN 3
6
(= Act2 16bit)
2)
Actual value 2 (torque)
5501 FBA DATA OUT 1
1
(= CW 16bit)
1)
Control word
5502 FBA DATA OUT 2
2
(= Ref1 16bit)
1)
Reference 1 (speed)
5503 FBA DATA OUT 3
3
(= Ref2 16bit)
2)
Reference 2 (torque)
5127 FBA PAR REFRESH 1
= REFRESH
Validates the FPBA-01
configuration parameter
settings.
9904 MOTOR CTRL
MODE
2
= VECTOR:
TORQ
Selects the vector control
mode as the motor control
mode.
1001 EXT1 COMMANDS
10
= COMM
Selects the fieldbus
interface as the source of
the start and stop
commands for external
control location 1.
1002 EXT2 COMMANDS
10
= COMM
Selects the fieldbus
interface as the source of
the start and stop
commands for external
control location 2.
1102 EXT1/EXT2 SEL
8
= COMM
Enables external control
location 1/2 selection
through the fieldbus.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus
reference 1 as the source
for speed reference 1.
1106 REF2 SELECT
8
= COMM
Selects the fieldbus
reference 2 as the source
for speed reference 1.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus
interface as the source for
the inverted Run enable
signal (Run disable).
Drive parameter
Setting for
ACS355 drives
Description
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...