Start-up 59
Starting up ACSM1 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter
50.01 FBA ENABLE
to Enable.
3. With parameter
50.02 COMM LOSS FUNC
, select how the
drive reacts to a fieldbus communication break.
Note that this function monitors both communication between
the fieldbus master and the adapter module and
communication between the adapter module and the drive.
4. With parameter
50.03 COMM LOSS T OUT
, define the time
between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.04
…
50.11
. Examples of appropriate values are shown in
the tables below.
6. Set the FPBA-01 configuration parameters in group 51. At the
minimum, set the required node address in parameter
51.02
and the communication profile in
51.05
.
7. Define the process data transferred to and from the drive in the
FPBA-01 configuration parameter groups 52 and 53.
Note:
The adapter module sets the Status word and Control
word automatically in parameters
52.01
and
53.01
.
8. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter
51.27 FBA PAR REFRESH
to
REFRESH.
9. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...