162 Communication protocol
Parameter data transfer examples (DP-V1)
The following examples show how parameter data is transferred
using the DP-V1 mechanisms READ and WRITE.
Note:
Only the “data unit” part of the SD2 telegram is presented in
the examples. See
PROFIBUS SD2 telegram for SAP 51
on page
Example 1a: Reading a drive parameter (array element)
Drive parameters are addressed so that the drive parameter group
corresponds to the
Parameter index
(PNU), and the drive
parameter number within the group corresponds to the
Subindex
(IND). In the following example, a value is read from drive
parameter number
12.04
(0C.04h).
•
DP-V1 Write request (Read parameter value):
90h
Illegal Request ID
The request ID of the response is
illegal.
96h
Internal buffer
Buffer overflow
A0h
Internal communication
Communication error between the
module and the drive
DP
header
5F 01 2F 0A 05 01 01 01 10 01 00 0
C
00 04 DP
trailer
DP-V1
Command
PROFIdrive V3 Parameter Channel
Error #
Meaning
Used at
Function number
Slot number
Index
Data length
Request reference
Request ID (01h= Request Parameter
Drive object ID
Number of parameters
Attribute (10h = Value)
Number of elements
Parameter index
Subindex
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...