112 Communication profiles
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be active;
see drive documentation. If the drive is
set to receive the Run enable signal from
the fieldbus, this bit activates the signal.
0
Inhibit operation. Proceed to
OPERATION INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP
FUNCTION GENERATOR: OUTPUT
ENABLED
.
0
Force Ramp Function Generator output to
zero. Drive ramps to stop (current and DC
voltage limits in force).
5
RAMP_HOLD 1
Enable ramp function.
Proceed to
RAMP FUNCTION
GENERATOR: ACCELERATOR
ENABLED
.
0
Halt ramping (Ramp Function Generator
output held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Force Ramp Function Generator input to
zero.
7
RESET
0
→
1
Fault reset if an active fault exists.
Proceed to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Continue normal operation.
8…9
Drive-specific (For information, see the drive documentation)
Bit
Name
Value
STATE/Description
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...