Communication profiles 111
ABB Drives communication profile
Control word and Status word
The Control word is the principal means for controlling the drive
from a fieldbus system. It is sent by the fieldbus master station to
the drive through the adapter module. The drive switches between
its states according to the bit-coded instructions in the Control
word and returns status information to the master in the Status
word.
The contents of the Control word and the Status word are detailed
below. The drive states are presented on page
Control word contents
The table below shows the contents of the Control word for the
ABB Drives communication profile. The upper case boldface text
refers to the states shown on page
.
Bit
Name
Value
STATE/Description
0
OFF1_
CONTROL
1
Proceed to
READY TO OPERATE
.
0
Stop along currently active deceleration
ramp. Proceed to
OFF1 ACTIVE
; proceed
to
READY TO SWITCH ON
unless other
interlocks (OFF2, OFF3) are active.
1
OFF2_
CONTROL
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON INHIBITED
.
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined
by drive parameter. Proceed to
OFF3
ACTIVE
; proceed to
SWITCH-ON
INHIBITED
.
Warning:
Ensure that motor and driven
machine can be stopped using this stop
mode.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...