130 Communication protocol
9
DPV1_Status_3 (DP-V1 only)
10
1Bh
(Default)
Structured_Length
Length of the structured Prm telegram. (User parameter
length is 23 bytes + 4 header bytes.)
11
81h
Structure_Type
129: USER_PRM_DATA
12
0
Slot_Number
Set to 0
13
0
Reserved
0 0 0 x 1 x x x
Alarm_Mode
.
Not supported.
Limits the number of
active alarms.
0 = 1 alarm of each type
1 = 2 alarms in total
2 = 4 alarms in total
3 = 8 alarms in total
4 = 12 alarms in total
5 = 16 alarms in total
6 = 24 alarms in total
7 = 32 alarms in total
MSB
LSB
Prm_Structure
0 = Prm telegram
according to EN 50170
1 = Prm telegram in
structure form (DPV2
extension)
Reserved.
To be parameterized with
‘0’.
IsoM_Req
(Isochron Mode Request)
Not supported.
0 = Isochron Mode
disabled
1 = Isochron Mode
enabled