Start-up 77
The start sequence for the parameter example above is given
below.
10.01 Ext1 start func
FB
Selects the fieldbus interface
as the source of the start and
stop commands for external
control location 1.
10.08 FAULT RESET
SEL
P.FBA MAIN
CW.8
Selects fieldbus interface as
the source for fault reset.
21.01 Speed ref1 sel
(ACS850)
21.01 Speed ref sel
(ACQ810)
FBA ref1
FBA ref1
Selects the fieldbus reference 1
as the source for speed
reference 1.
1)
Read-only or automatically detected/set
2)
Example
Control word
Start sequence
47Eh (1150 decimal)
READY TO SWITCH ON
47Fh (1151 decimal)
OPERATING (Speed mode)
Drive parameter
Setting for
ACS850/
ACQ810 drives
Description