Start-up 53
Parameter setting examples – ACS355
Speed control using the PROFIdrive communication profile
with PPO Type 2
This example shows how to configure a basic speed control
application that uses the PROFIdrive profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the
PROFIdrive profile. For more information, see the PROFIdrive
state machine on page
The reference value ±16384 (4000h) corresponds to parameter
1105 REF1 MAX
in the forward and reverse directions.
The table below gives the recommended drive parameter settings
Direction PZD1
PZD2
PZD3
PZD4
PZD5 PZD6
Out
Control
word
Speed
reference
Constant
speed 1
1)
Constant
speed 2
1)
N/A
N/A
In
Status
word
Speed
actual
value
Power
1)
DC bus
voltage
1)
N/A
N/A
1)
Example
Drive parameter
Setting for
ACS355 drives
Description
9802 COMM PROT SEL
4
= EXT FBA
Enables communication
between the drive and the
fieldbus adapter module.
5101 FBA TYPE
PROFIBUS-DP
1)
Displays the type of the
fieldbus adapter module.
5102 FB PAR 2
(NODE ADDRESS)
3
2)
Defines the PROFIBUS
node address of the
fieldbus adapter module.
5103 FB PAR 3
(BAUD RATE)
12000
1)
Displays the current baud
rate on the PROFIBUS
network in kbit/s.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...