102 Communication profiles
2
OFF3
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop according to fastest
possible deceleration mode. Proceed to
OFF3 ACTIVE
; proceed further to
SWITCH-ON INHIBIT. Warning:
Ensure
motor and driven machine can be stopped
using this stop mode.
3
OPERATION_
ENABLE
1
Proceed to
ENABLE OPERATION
.
0
Inhibit operation. Proceed to
OPERATION
INHIBIT
.
4
ENABLE_
RAMP_
GENERATOR
or
1
Normal operation.
Proceed to
RAMP
FUNCTION
GENERATOR:
ENABLE OUTPUT
.
Normal operation.
Do not reject
traversing task.
TRAVERSING
_TASK
0
Stop according to
selected stop type.
Reject traversing
task.
5
1
Normal operation.
Proceed to
RAMP
FUNCTION
GENERATOR:
ENABLE
ACCELERATOR
.
Normal operation.
No intermediate
stop.
0
Halt ramping (Ramp
Function Generator
output held).
Intermediate stop
Bit
Name
Value
STATE/Description
Speed control
mode
Positioning mode