72 Start-up
The start sequence for the parameter example above is given
below.
Setting up the drive for fieldbus control manually
The fieldbus adapter module is typically pre-installed. The device
automatically recognizes the module. If the adapter is not pre-
installed, you can install it mechanically and electrically.
1. Install the fieldbus adapter module mechanically and electrically
according to the instructions given in the user’s manual of the
module.
2. Power up the drive.
3. Enable the communication between the drive and the fieldbus
adapter module with parameter
50.01 FBA A enable
.
4. With parameter
50.02 FBA A comm loss func
, select how the
drive should react to a fieldbus communication break.
Note
: This function monitors both the communication between the
fieldbus master and the adapter module and the communication
between the adapter module and the drive.
5. With parameter
50.03 FBA A comm loss t out
, define the time
between communication break detection and the selected action.
6. Select application-specific values for rest of the parameters in
group
50 Fieldbus adapter (FBA)
, starting from parameter
50.04
.
Examples of appropriate values are shown in the tables below.
7. Set the fieldbus adapter module configuration parameters in
group
51 FBA A settings
. As a minimum, set the required node
address and the communication profile.
8. Define the process data transferred to and from the drive in
parameter groups
52 FBA A data in
and
53 FBA A data out
.
Note
: Depending on the communication protocol and profile being
used, the Control word and Status word may already be configured
to be sent/received by the communication system.
Control word
Start sequence
47Eh (1150 decimal)
READY TO SWITCH ON
47Fh (1151 decimal)
OPERATING (Speed mode)
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...