78 Start-up
Starting up ACS880 and ACS880-M04 drives
1. Power up the drive.
2. Enable communication between the adapter module and the
drive by setting parameter
50.01 FBA A Enable
, option slot 1,
2 or 3 depending on the slot the adapter module is attached to.
3. With parameter
50.02 FBA A comm loss func
, select how the
drive reacts to a fieldbus communication break.
Note
: This function monitors communication both between the
fieldbus master and the adapter module and between the
adapter module and the drive.
4. With parameter
50.03 FBA A comm loss t out
, define the
time between communication break detection and the selected
action.
5. Select application-specific values for the rest of the parameters
in group 50, starting from parameter
50.04 FBA A ref1 type
.
Examples of appropriate values are shown in the tables below.
6. Set the FPBA-01 configuration parameters in group 51. At the
minimum, set the required node address in parameter
51.02
Node address
and the communication profile in
51.05 Profile
.
7. Define the process data transferred to and from the drive in
FPBA-01 configuration parameter groups 52 and 53.
Note:
The adapter module sets the Status word and Control
word automatically in parameters
52.01 FBA A data in1
and
53.01 FBA A data out1
.
8. Save the valid parameter values to permanent memory by
setting parameter
96.07 Parameter save manually
to Save.
9. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter
51.27 FBA A par refresh
to Refresh.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...