Communication protocol 121
PROFIBUS SD2 telegram for Default SAP (0) and SAP 58-62
PROFIBUS typically uses SD2 telegrams for DP communication.
The structure of an SD2 telegram is shown below.
Default SAP (SAP 0) (Data_Exch)
This SAP allows the master to send output data to a slave station
and to simultaneously request input data from the same station.
In addition to Default SAP, any master can read the I/O data of any
slave at any time using the “Read_Inputs” (SAP 56) and
“Read_Outputs” (SAP 57) telegrams. These telegrams have
otherwise the same structure as the cyclic Data_Exchange
telegram, but include the DSAP and SSAP bytes. In these
telegrams, the MSB of the DA and SA bytes is set to 1 to indicate
that a DSAP/SSAP byte follows in the telegram header.
Output Data
Input Data
Data
Outp_Data
Inp_Data
DU length
4 to 32 bytes (depending on the selected PPO
message or standard telegram type)
DP header
DP trailer
SD LE
LEr SD DA SA FC *DSAP *SSAP DU FCS
ED
68h x
x
68h xx
xx
x
xx
xx
x… xx
16h
SD = Start delimiter
LE = Length
LEr = Length repeated
DA = Destination address
SA = Source address
FC = Function code
*DSAP = Destination service access point
*SSAP = Source service access point
DU = Data unit for DP services
FCS = Frame checking sequence
ED = End delimiter
*Not present with Default SAP (0)
Data unit
See the descriptions of each SAP on the following pages.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...