2.5.2 Molded-case Circuit Breaker and Fuse Capacity
2-28
2.5.2 Molded-case Circuit Breaker and Fuse Capacity
* 1. Nominal value at the rated load. The specified derating is required to select an appropriate fuse
capacity.
* 2. Cutoff characteristics (25
°
C): 300% five seconds min. and inrush current of 20 ms.
* 3. Make sure the current capacity is accurate. For the SERVOPACK with the cooling fan built-in, an
inrush current flows; 200% of the current capacity in the table above for two seconds, when turning ON
the control circuit power supply to start the fan working.
Note: Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor input type, a
fast-acting fuse may blow when the power is turned ON.
The SGDM SERVOPACK does not include a protective grounding circuit. Install a ground-fault protector to
protect the system against overload and short-circuit or protective grounding combined with the molded-case
circuit breaker.
Main
Circuit
Power
Supply
SERVOPACK Model
Power Supply
Capacity per
SERVOPACK
(kVA)
Current Capacity of the
Molded-case Circuit Breaker
and the Fuse (A
rms
)
*1, *2
(
Refer to 5.8.9
)
Inrush Current
Capacity
(kW)
SGDM
-
Main Circuit
Power Supply
Control Cir-
cuit Power
Supply
Main Circuit
Power Supply
Control Cir-
cuit Power
Supply
Single-
phase
100 V
0.03
A3BD, A3BDA
0.15
4
0.26
32A
30A
0.05
A5BD, A5BDA
0.25
0.10
01BD, 01BDA
0.40
0.20
02BD, 02BDA
0.60
6
Single-
phase
200 V
0.03
A3AD, A3ADA
0.20
4
0.13
63A
60A
0.05
A5AD, A5ADA
0.25
0.10
01AD, 01ADA
0.40
0.20
02AD, 02ADA
0.75
0.40
04AD, 04ADA
1.2
8
Three-
phase
200 V
0.45
05AD, 05ADA
1.4
4
0.15
∗
3
118A
60A
0.75
08AD, 08ADA
1.9
7
1.0
10AD, 10ADA
2.3
1.5
15AD, 15ADA
3.2
10
2.0
20AD, 20ADA
4.3
13
63A
3.0
30AD, 30ADA
5.9
17
5.0
50ADA
7.5
28
67A
6.0
60ADA
12.5
32
0.27
∗
3
40A
7.5
75ADA
15.5
41
11.0
1AADA
22.7
60
0.3
∗
3
80A
15.0
1EADA
30.9
81