6 Wiring
6.4.4 Installation Conditions of UL Standards
6-24
(c) Fixing the Cable
Fix and ground the cable shield using a piece of conductive metal.
• Example of Cable Clamp
(d) Shield Box
A shield box, which is a closed metallic enclosure, should be used for shielding magnetic interference. The
structure of the box should allow the main body, door, and cooling unit to be attached to the ground. The box
opening should be as small as possible.
6.4.4 Installation Conditions of UL Standards
To adapt the following SERVOPACKs to UL Standards, use a corresponding terminal kit for cables to connect
the terminals described in the table below.
Main Circuit Wiring
1. SGDM SERVOPACKs are suitable under the following conditions.
• With 200 V class: Less than 5000 A
rms
, 240 V maximum.
• With 400 V class: Less than 5000 A
rms
, 480 V maximum.
2. SERVOPACKs must be used with UL-listed fuses or circuit breakers, in accordance with the National
Electrical Code (NEC).
3. Use 75
°
C heat-resistant copper wires or an equivalent.
Host controller side
Ground plate
Cable
Cable
clamp
Shield (cable sheath stripped)
Fix and ground the cable shield
using a piece of conductive metal.
Remove paint on mounting surface.
SERVOPACK Model
Connection Terminals
Terminal Kit Model
SGDM-50ADA (-R)
L1, L2, L3
(Main circuit power supply input)
U, V, W (Motor Output)
JZSP-CKT75
SGDM-60ADA (-P)
JZSP-CKT75
SGDM-75ADA (-P)
JZSP-CKT75
SGDM-1AADA (-P)
JZSP-CKT75
SGDM-1EADA (-P)
JZSP-CKT1E