Brine Fogging System Type SOLFOG V3
Index: 02
Change date: 19/09/2023
OI No.: BA DW 042-02 Solfog V3 CB36 EN.docx
Page 40 of 65
8.7.5
Set operation modes
The 3 operation modes
Requirement for all operation modes:
The operating contact must be closed.
The switch times must be set on the week days if the timer is activated.
Auto: Once switched on, the device works with the internal settings (fogging time, pause
time, timer).
Externally: The device can be activated (fog on) or deactivated (standby position) via an ex-
ternal contact (e.g., higher-level control such as WDT central control). As long as the contact
is closed, fog is generated.
The dosing time and pause time can be specified with a higher-level control
The external contact is not active when the operation mode
Auto
or
Push button
has been
selected.
Push button: In push-button operation, the fogging is started via the push-button (option) in
the cabin and operated for the set push-button cycle time, with the settings of the pause and
fogging time.
8.7.6
Set push button cycle
Fig. 49: Illustration push button cycle
Fig. 47: Menu: Operation mode
1)
Select the
Operation mode
entry in the main menu
and confirm with the Enter key
.
2)
Select the operation mode using the arrow keys and
save with the Enter key
.
The display returns to the main menu.
Fig. 48: Menu: Push button cycle
The push button cycle is the period during which the set
fogging and pause times run in a repeated cycle until the
time period has expired (Fig. 49). The time period (push
button cycle) can only be set in the Push button operation
mode. The push button cycle can only be started by press-
ing the push button.
1)
Select the
Push button cycle
entry in the main
menu and confirm with the Enter key
.
2)
First set the minutes using the arrow keys, confirm the
entry with the Enter key
, then set the seconds and
save with the Enter key
.
The display returns to the main menu.
Push button cycle
Pause time
Fogging time